The silicon-based CARBOCAP® sensor delivers high accuracy and long-term measurement stability (±100 ppm) over a five-year period without calibration. The
diffusion-aspirated, single-beam, dual-wavelength sensor structure is remarkably simple. It consists of an infrared (IR) source, a sample cell, an IR detector, and
a tunable interference filter that enables measurements at two wavelengths. Reference measurements made using a tunable interference filter eliminate the typical weakness of dual-beam sensors and permits shifting the optical pass band electronically. This innovative design provides precise reference readings that eliminate the typically broad deviation expected from a traditional CO2 sensor.
Features
• DCV strategies offer a potential for 10 to 70% energy savings
• CARBOCAP single-beam, dual-wavelength design provides superior performance compared to other technologies
• CARBOCAP silicon, micro-machined construction provides reliable CO2 measurement in duct environments
• calibration reliability offers five years of reliable calibration
• adjustable duct probe depth permits optimal placement of sensing tip in a duct
• optional features offer relay output for fan control
Inquiry - Duct Mount CO2 Transmitter (CD-Pxx-00-0 Series)