• Built-in relays
• Control switches on the front panel
• Analogue outputs with possibility of manual
control
• Simple wiring
• Easy to install in a standard casing
Inputs and outputs
IO-4X4-M has 16 in- and outputs. 4 digital inputs with pulse counting Indication via LEDs.
4 digital outputs
With manual switch, LEDs and potential-free closing contact.
4 analogue inputs
Support PT1000, Ni1000 (only CAN-Bus), microsensors, 0...10 V, 0...20 mA and 0...10 kΩ.
4 analogue outputs
0...10 V with possibility of manual operation via switches.
Inquiry - IO-4X4-M